Release Notes: Intelli-Site 4.2.11.15
Created: 06-03-2025 12:23 PMLast Updated: 06-03-2025 12:42 PM

Operating Systems No Longer Supported

As of January 14, 2020, Microsoft Windows 7 and Windows Server 2008 R2 have reached end-of-life. Microsoft no longer supports these OSes. As such, OSSI no longer supports these operating systems. While our software will continue to install and upgrade on Windows 7 and Windows Server 2008 R2, we will not provide technical support for these systems for versions beyond Intelli-Site v4.0.45.12.  All customers and integrators are strongly encouraged to migrate to Windows 10 or Windows 2016.

Overview

This article contains the release notes for Intelli-Site v4.2.11.15. The following sections describe the release in detail and provide late-breaking or other information that supplements the main documentation.

Upgrade Requirements

Because the database has been redesigned, the installer will only upgrade version 4.0.45.12 or later. Minor modifications to the database had been implemented before version 4.0.45.12. Those modifications must be applied to the existing database for the software upgrade to properly upgrade the database.

The process is:

  1. Upgrade to version 4.0.45.12
  2. Open the Configuration Utility and start the Engine. The Engine performs the necessary modifications, not the installer. If there are multiple projects, each project must be started.
  3. Stop the Engine and close the Configuration Utility.
  4. Upgrade to the current version.
  5. Open the Configuration Utility and start the Engine. As stated in step 2, the Engine performs the necessary database upgrade not the installer. If there are multiple projects, each project must be started as well.

NEW FEATURES

The following software features were added

  • Database
    • No changes.
  •  Documentation
    • No changes.
  • General
    • Event Formatter: Added the ability to send HTTP Post, Put, and Get messages.
    • Event Formatter: Added the Event Format Builder.
      • This builds the Format strings for you based on fields you select.
  • Desktop Client 
    • Information Manager Layouts: Added the ability to set the height and width of buttons in the Alarm Status Queue.
    • Added the ability to email a Custom Master History Report.
      • Must first target a Distribution List with the SetOn action. Then, target a Custom Master History report settings node with the EmailReport action.
    • Access Management: Added the ability to search for vehicles.
    • Implemented Screen List Control/Display Creation
    • Design View: Add shortcut keys for toolbar buttons.
      • Hover your mouse over buttons to see the tooltip showing the assigned shortcut keys.
  • Reports
    • No changes.

The following Panels were added or upgraded:

  • SNMP
  • Harding DXL
    • Import now includes Paging Zones
  • OPC DA
    • SetOn/Off/Pulse are now allowed for non Boolean tags.

RESOLVED ISSUES

The following issues affecting all products have been resolved:

  • Configuration Utility
    • Note: Do not start the Client Manager unless you absolutely need it. Only start it when redundant Engines are required and licensed. The Client Manager counts as a client in the license.
      This isn't new. It just bears repeating.
  • Desktop Client
    • Running a report against a report settings node always prompts for date/time.
      • Now, only reports settings nodes with a Custom date/time will prompt.
    • Error when attempting to edit an existing scheduled event.
    • Error when using the FilterSet action.
  • Driver Specific
    • ASSA ABLOY Aperio: The Card Config Screen is not wide enough to see all fields.
    • ASSA ABLOY Aperio: The Access Group node is not created if not using Global Timezones.
    • Axis Media Control: Do not allow Import From NVRcameras that include the "@" symbol in their password.
    • MAC: Create Multiple Templates causes an error.
    • Vicon Valerus: Driver service exception when disabling driver.

The following issues specific to Intelli-Site Lite have been resolved:

  • N/A

Below are issues related to specific OEM versions: